Where are exit signs required?
NFPA 101 Section 7.10 (Marking of Means of Egress) requires exit signs at every exit door, at every change of direction along the path of travel to an exit, at the top of every required exit stair (and bottom in some configurations), and wherever the path of egress is not otherwise obvious. The IBC Section 1013 mirrors these requirements. The general rule of thumb is that an occupant standing anywhere in an exit-access corridor should be able to see at least one exit sign from any point and never have to travel more than 100 ft without seeing a sign indicating the direction of the exit. Specific exemptions exist for very small occupancies (typically less than 50 occupants), residential dwelling units, and certain industrial areas where the building is so simple that the exit is obviously visible. Conversely, large occupancies like assembly halls and theaters often need supplementary low-level signs that remain visible if smoke fills the upper portion of the room. The posted evacuation plan should show every exit-sign location with the appropriate icon (NFPA 170 exit symbol or ISO 7010 E001/E002 running man).
What are the illumination requirements?
NFPA 101 Section 7.10.5 sets the illumination standard: the sign must be illuminated whenever the building is occupied, with a minimum face luminance of 0.06 footlambert (0.2 cd/m²). The contrast ratio between the sign letters and the background must be at least 0.5. Two illumination methods are recognized — externally illuminated signs (a separate light source illuminates the face of the sign) and internally illuminated signs (light sources inside the sign housing). Externally illuminated signs must achieve at least 5 footcandles (54 lux) on the sign face. Internally illuminated signs are usually LED-based today; older fluorescent and incandescent designs are being phased out as LED retrofits become economical. The sign must also remain visible under emergency conditions: NFPA 101 Section 7.10.7 requires that exit signs be supplied by both the primary building electrical system and an emergency power source (battery or generator) capable of operating the sign for at least 90 minutes after primary power loss. The IBC adopts the same 90-minute duration.
What are the size, lettering and color rules?
NFPA 101 Section 7.10.6 specifies sign dimensions and lettering: the word EXIT must be in legible letters not less than 6 inches high, with strokes not less than 3/4 inch wide, and minimum spacing of 3/8 inch between letters. Directional indicators (arrows) must be at least 1 inch wide. The sign face must contrast against its background — the rule is that the lettering color contrast against the sign background must achieve at least 50% (the 0.5 ratio noted above). NFPA 101 explicitly permits either red or green lettering; the IBC permits red, green or other colors meeting the contrast requirement. Green is the international standard (ISO 7010) and is increasingly common in U.S. installations; red remains the historical U.S. norm. Pictographic exit signs using the green running-man icon are accepted under both NFPA 101 (in addition to the worded sign) and the IBC. The posted evacuation plan typically uses a generic exit icon in the MAP KEY rather than reproducing the lettering of the physical sign, since the icon is what the viewer sees on the plan.
What about photoluminescent and low-location exit signs?
Photoluminescent (PL) signs use phosphorescent pigments that absorb ambient light and re-emit it as visible light in darkness, requiring no electrical connection. NFPA 101 recognizes PL signs as a permitted method of illumination provided the sign meets the same luminance requirements and is exposed to a minimum of 5 footcandles of ambient light at the sign face when the building is occupied. PL signs are widely used in high-rise stairwells under New York City Local Law 26 (post-2007) and similar regulations, where they provide low-location egress marking that remains visible in smoke-filled environments where overhead signs may be obscured. ASTM E2073 is the test method for PL luminance decay. Low-location lighting under NFPA 101 Section 7.10.1.7 (high-rise life safety) is a supplementary system installed not more than 18 inches above the floor in exit stair enclosures, providing continuous wayguidance along the entire egress path through the stair. The posted plan should note the use of PL or low-location systems in the legend so occupants know what to look for during a smoke event.
What battery backup and testing is required?
Exit signs and emergency illumination must remain operational for 90 minutes after loss of normal power under NFPA 101 Section 7.10.7 and IBC Section 1013.6. The 90-minute duration is also referenced in NFPA 70 (National Electrical Code) Article 700 (Emergency Systems) and NFPA 110 (Standard for Emergency and Standby Power Systems). Battery backup is the most common solution for individual signs; central-inverter or generator-backed systems are used in large buildings. Testing is required under NFPA 101 Section 7.9.3: monthly functional test of at least 30 seconds, and annual test of full 90-minute duration. The test is documented in the facility's life-safety log. Self-diagnostic LED exit signs that perform automatic monthly and annual tests are increasingly popular and significantly reduce the labor associated with manual testing. Failure of an exit sign during testing requires repair or replacement before the next test cycle. The posted evacuation plan does not include test status, but the facility manager responsible for the plan should ensure that the inventory of signs on the plan matches the inventory in the test log.
How are direction-only and tactile signs handled?
Some egress paths require directional-only signs (an arrow without the word EXIT) at a junction where the exit is around a corner. NFPA 101 permits direction-only signs subject to the same illumination requirements as standard exit signs. The IBC adds that direction-only signs must clearly indicate the path to the exit at every change of direction. Tactile exit signs under ADA 2010 Standards Section 703 are required at doors leading to means of egress — a sign with raised characters and Braille mounted on the wall adjacent to the latch side of the door, at 48 inches above the floor to the bottom of the highest line of text. The tactile sign typically reads simply EXIT or EXIT ROUTE and is in addition to the illuminated overhead sign. Stair identification signs under IBC Section 1023.9 mark each stair with its identifier (Stair A, Stair B), the floor number, the direction of exit discharge and the upper/lowermost floors of access; these are tactile signs mounted at every floor level inside the stair enclosure. The posted plan should depict stair identifiers so occupants can navigate to a specific stair if directed by responders.
How does EvacPlan Generator handle exit signs?
EvacPlan Generator (www.evacplangenerator.com) provides an Exit icon and an Exit-with-arrow icon in the standard symbol library, plus the ISO 7010 green running-man pictogram for international or pictogram-preferred plans. Each exit door drawn on the floorplan can be marked with an icon, and directional arrows can be added at corridor turns to indicate the path of travel. The route-line tool draws the actual egress path from any starting room to the exit, with optional arrowheads at intervals. Stair identifiers can be added as text annotations next to each stair on the plan. For high-rise plans the planner can note the use of photoluminescent low-location lighting in the MAP KEY by adding a textual legend item. Plans for buildings under jurisdictions that require pictogram-only exit signs (most international) versus worded signs (traditional U.S.) can be produced in parallel using the same underlying floorplan. The PDF export preserves color and contrast so the printed plan accurately represents the building's exit-sign configuration.